CDLD Impulse Current Generator For Test Residual Voltage And Motion Load Of Valve Discs
CDLD series
The CDLD impulse current generator is featured by wide range of applicable wave forms. It is mainly used to test the residual voltage and motion load of valve discs, unit modules and SPDs. It is also used for routine test of HV apparatus manufacturers.
Main features:
Product |
D type impulse current generator |
|
Type |
CDLD |
|
Structure |
D type |
Each unit consists of 2-4 horizontal large capacitors laid on the frame, a multi-tap inductor is vertically installed above the sphere gap; 2-6 units are laid around the sphere gap in D pattern; inductors can be adjusted according to wave form and test object resistive during tests |
Functions |
It is mainly used to test the residual voltage and motion load of valve disc, arrestor and SPDs. |
|
Advantages |
Good appearance |
As shown in the photo |
Module design |
The charging unit, resistors, capacitor frame, sphere gap are separate functional modules for easy reconfiguration and repair. |
|
Flexible combination |
Flexible combination of different units and within the units enables generating wave forms of different energy. |
|
Easy modulation |
Flexible combination of inductors and capacitors for easy modulation |
|
Compact design |
Spark gap cylinder, test bay, measuring components are assembled on a base frame; compact design and low inductance |
|
Stable and reliable triggering |
Durable graphite spark gaps; gap distance is adjusted by a drive motor; impulse firing available with stable triggering |
|
Mobility |
Universal wheels on each module for easy displacement |
|
Stable performance |
Long-time operation at a voltage lower than 80% of rated voltage |
|
Performance |
Current impulse |
4/10μS |
8/20μS |
||
30/80μS |
||
10/350μS |
||
1000/2000μS |
||
The impulse current generator and the charging unit are separate. |
||
Charging unit with dual voltagerectification |
||
Charging unit with automatic grounding and polarity reversal (external) |
||
Encapsulated spark gaps with less noise |
||
Capacitor with grounding device |
||
Rogwoski circuits and dividers |
||
Leading technologies and performance |
Specifications:
Type |
Rated current(kA) |
Total energy(kJ) |
Wave form(μS) |
NO. of capacitors (n) |
Main test objects |
CDLD20/100 |
20 |
100 |
30/80,8/20 |
4 |
Valve disc, unit module |
CDLD40/240 |
40 |
240 |
30/80,1000/2000 |
24 |
Valve disc, unit module |
CDLD100/108 |
100 |
108 |
4/10,8/20,30/80 |
4 |
Valve disc, unit module |
CDLD80/108 |
80 |
108 |
8/20,10/350 |
6 |
Valve disc, SPD |
CDLD100/180 |
100 |
180 |
8/20,10/350 |
12 |
Valve disc, SPD |
HiWING Mechanical & Electrical Technology Corp , [China (Mainland)]
Business Type:Manufacturer
City: Beijing
Province/State: Beijing
Country/Region: China (Mainland)